Parameters A - 14

Digital Inputs

H1-04

Terminal S6 Function
Selection
Terminal S6 Sel

1E: Ref Sample Hold
Analog speed command is sampled then held at time of input

closure.

20: External fault, Normally Open, Always Detected, Ramp To

Stop

21: External fault, Normally Closed, Always Detected, Ramp To

Stop

22: External fault, Normally Open, During Run, Ramp To Stop
23: External fault, Normally Closed, During Run, Ramp To Stop
24: External fault, Normally Open, Always Detected, Coast To

Stop

25: External fault, Normally Closed, Always Detected, Coast To

Stop

26: External fault, Normally Open, During Run, Coast To Stop
27: External fault, Normally Closed, During Run, Coast To Stop
28: External fault, Normally Open, Always Detected, Fast-Stop
29: External fault, Normally Open, Always Detected, Fast-Stop
2A: External fault, Normally Open, During Run, Fast-Stop
2B: External fault, Normally Closed, During Run, Fast-Stop
2C: External fault, Normally Open, Always Detected, Alarm Only
2D: External fault, Normally Closed, Always Detected, Alarm

Only

2E: External fault, Normally Open, During Run, Alarm Only
2F: External fault, Normally Closed, During Run, Alarm Only
34: PI SFS Cancel
36: Option/Inv Sel 2 Selects source of speed command and

sequence

Closed = b1-01 & b1-02, Open = Option Card
60: Motor Preheat Applies current to create heat to avoid

condensation.

Closed = Apply amount of current as set in parameter b2-09
61: Speed Search 1
When closed as a run command is given, Drive does a speed
search starting at maximum frequency (E1-04).

(Current detection)

62: Speed Search 2
When closed as a run command is given, Drive does a speed
search starting at speed command. (Current detection).
64: Speed Search 3
67: Com Test Mode - Used to test RS-485/422 interface.
68: High Slip Braking - Closed = Drive stops using High Slip

Braking regardless of run command status.

69: Jog2 - Closed = Drive runs at speed command entered into

parameter d1-17.

Direction determined by fwd/rev input. 3-wire control Only.
6A: Drive Enable - Closed = Drive will accept run command.
Open = Drive will not run. If running, Drive will stop per

b1-03.

6B: Com/Inv Sel - Selects source of speed command and sequence
Closed = Serial Communication (R+,R-,S+,S-), Open = b1-01

& b1-02

6C: Com/Inv Sel 2
6D: Auto Mode Sel - Hand/Auto Selection - Closed = Auto,

Open = Hand

6E: Hand Mode Sel - Hand/Auto Selection - Closed = Hand,

Open = Auto

70: Bypass Drv Enbl

0 to 6E

4: 2-wire
3: 3-wire

Programming

H1-05

Terminal S7 Function
Selection
Terminal S7 Sel

0 to 6E

6: 2-wire
4: 3-wire

Programming

Table 1: Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location