2 dead zone b instruction (dzb), Real number type operation, Outline – Yaskawa MP900 Series Machine Controller New Ladder Editor User Manual

Page 132

Advertising
background image

1 Ladder Program Instructions

1.7.2 DEAD ZONE B Instruction (DZB)

1-122

Real Number Type Operation

1.7.2 DEAD ZONE B Instruction (DZB)

„

Outline

The DZB instruction executes a dead zone operation on integer, double-length integer or real
number data.

The following operation is performed, where Input is the input value, Zone is the designated
dead zone value, and Output is the output value:

Output

= Input - the absolute value of Zone (the absolute value of Input is greater than or

equal to the absolute value of Zone; Input is greater than or equal to 0)

Output

= Input + the absolute value of Zone (the absolute value of Input is greater than

or equal to the absolute value of Zone; Input is less than or equal to 0)

Output

= 0 (the absolute value of Input is less than the absolute value of Zone)

Outside

dead zone

Within

dead zone

X

Y

+D

-D