1 Ladder Program Instructions

1.7.12 LINEAR ACCELERATOR/DECELERATOR 2 Instruction (SLAU)

1-158

* Relay I/O Bit Assignment

The following operations are performed inside integer type SLAU instructions.

Integer Type SLAU Instruction

BIT

Symbol

Name

Specifications

I/O

0

RN

Line is running

"ON" is input while the line is running.

IN

1

QS

Quick stop

"OFF" is input upon quick stop.

IN

2 to 7

(Reserved)

Reserved relay for input

IN

8

ARY

In acceleration

"ON" is output during acceleration.

OUT

9

BRY

In deceleration

"ON" is output during deceleration.

OUT

A

LSP

Zero speed

"ON" is output upon attainment of a speed of 0.

OUT

B

EQU

Coincidence

"ON" is output when input value

= output value.

OUT

C to F

(Reserved)

Reserved relay for output

OUT

LV

× Ts (0.1 ms) + REM1 Outside S- curve area (ADVS > ADV)

Acceleration rate (ADV)

=

AT(0.1s)

× 1000

When VI > V (V

0)

V

= V + ADV: In acceleration (ARY)

ON

When VI < V (V

0)

V

= V - ADV: In acceleration (ARY)

ON

,

,

,

,

,

,

LV

× Ts (0.1 ms) + REM1 Outside S-curve area (BDVS > BDV)

Deceleration rate (BDV)

=

BT (0.1s)

× 1000

At VI > V (V < 0)

V

= V + BDV: In deceleration (BRY)

ON
When VI < V (V > 0)

V

= V - BDV: In deceleration

(BRY)

ON

,

,

,

,

,

,

LV

× Ts (0.1 ms) + REM1 When QS = ON (VI > V ) ,

Quick stop rate (QDV)

=

QT (0.1 s)

× 1000

ON
When QS = ON (VI < V’),

ON
(NOTE) The quick stop rate is not S -
curve movement, but linear movement
(same as the quick stop rate of SLAU).

V

= V + QDV: In deceleration(BRY)

,

V

= V - QDV: In deceleration(BRY)

,

,