1 Ladder Program Instructions

1.2.14 SPEND TIME Instruction (SPEND)

1-42

„

Parameter

* Possible to omit.

„

Program Example

The time elapsed from the time data in MW00100 to MW00103 to the time data in
DW00000 to DW00003 is stored to MW00100 - MW00105.

98 yrs 5 mos 11 days 15 hrs 4 min 47 sec - 98 yrs 4 mos 2 days 8 hrs 13 min 8 sec

(MW00100) (MW00101) (MW00102) (MW00103) (DW00000) (DW00101) (DW00102) (DW00103)

= 0 yrs 39 days 6 hrs 51 min 39 sec

(MW00100) (MW00101) (MW00102) (MW00103)

In the operation results, the year is counted as 365 days and a leap year is not taken into consideration.
Also, the number of months is not counted. It is counted in days.

Parameter Name

Setting

Source

• Any integer type register
• Any integer type register with subscript

Dest

• Any integer type register (except for # and C register)
• Any integer type register with subscript (except for # and C reg-

ister)

[Status]*

• Any bit type register (except for # and C register)
• Any bit type register with subscript (except for # and C register)

Time Data

Before Execution

After Execution

MW00100

H0098

H0000

MW00101

H0511

H0039

MW00102

H1504

H0651

MW00103

H0047

H0039

MW00104

−

3394299 (Decimal)

MW00105

−

DW00000

H0098

H0098

DW00001

H0402

H0402

DW00002

H0813

H0813

DW00003

H0008

H0008