Process Result (PARAM00)

The process result is output to the upper byte. The lower byte is for system analysis.

• 00xx: In process (BUSY)
• 10xx: End of process (COMPLETE)
• 8xxx: Occurrence of error (ERROR)

Error Classification

• 81xx: Function cord error

The sending of an unused function code was attempted. Or, an unused function code
was received.

• 82xx: Address setting error

The data address, coil offset, input relay offset, input register offset, or holding regis-
ter offset setting is out of range.

• 83xx: Data size error

The size of the sent or received data is out of range.

• 84xx: Line No. setting error

The line No. setting is out of range.

• 85xx: Channel No. Setting error

The channel No. setting error.

• 86xx: Station address error

The station No. setting is out of range.

• 88xx: Transmission unit error

An error response was returned from the transmission unit. (Refer to "„ Parameter
Details" (on page 2-14)).

• 89xx: Device selection error

A non-applicable device is selected.

PARAM 11

IN

Holding register offset

Register offset

PARAM 12

IN

Write-in range LO

Register offset

PARAM 13

IN

Write-in range HI

Register offset

PARAM 14

SYS

For system use

For system use

PARAM 15

SYS

System reserved

System reserved

PARAM 16

SYS

System reserved

System reserved

Table 2.7 Parameter List (cont’d)

Parameter No.

IN/OUT

Contents

MEMOBUS

Non-procedural