Parameter „ parameter details – Yaskawa MP900 Series Machine Controller New Ladder Editor User Manual

Page 207

Advertising
background image

2 Standard System Function

2.1.2 Receive Message Function (MSG-RCV)

2-14

„

Parameter

„

Parameter Details

They adhere to contents-functions and so on and are collected into parameter numerical
order.

Table 2.7 is Parameter List.

I/O

Definition

Parameter

Name

I/O

Designation

Setting

Input

Execute

B-VAL

Receive message instruction

Abort

B-VAL

Receive message forced interruption instruction

Dev-Typ

I-REG

Type of transmission device

CPU module

= 8

215IF

= 1

217IF

= 5

218IF

= 6

218-02 = 16

SVB-01

= 11

Pro-Typ

I-REG

Transmission protocol (Set up of RTU and ASCII is module configu-
ration definition.)

MEMOBUS

= 1

non-procedural

= 2

Cir-No

I-REG

Line No.

CPU module

= 1

215IF

= 1 to 8

217IF

= 1 to 24

218IF

= 1 to 8

SVB-01

= 1 to 16

Ch-No

I-REG

Transmission buffer channel No.

CPU module

= 1

215IF

= 1 to 13

217IF

= 1

218IF

= 1 to 10

SVB-01

= 1 to 8

Param

Address in-
put

Head address of set data (MW, DW, #W)

Output

Busy

B-VAL

Message is being received.

Complete

B-VAL

The receiving of the message has been completed.

Error

B-VAL

Occurrence of error

Table 2.7 Parameter List

Parameter No.

IN/OUT

Contents

MEMOBUS

Non-procedural

PARAM 00

OUT

Process result

Process result

PARAM 01

OUT

Status

Status

PARAM 02

OUT
IN

*

Called station number

Called station number

PARAM 03

SYS

System reserved

System reserved

PARAM 04

OUT

Function code

PARAM 05

OUT

Data address

Data address

PARAM 06

OUT

Data size

Data size

PARAM 07

OUT

Called CPU number

Called CPU number

PARAM 08

IN

Coil offset

PARAM 09

IN

Input relay offset

PARAM 10

IN

Input register offset

Advertising