1.7 DDC Instructions

1-137

1

Block Diagram

• When the P + I + D offset reaches the upper or lower PID limit (UL, LL) or the PID

dead band (DB)
When the present P offset and the I offset are the same in sign (diverging), the I offset is
not renewed but is kept at the previous value. Oppositely, if the P and I offsets are oppo-
site in sign (converging towards 0), the I offset is renewed with the present value.

• When the change in deviation output (X-X’) and the previous deviation input X’

are the same in sign (diverging) in the differential (D) operation
The divergence differential time (Td1) is used as the differential time.

• When the change in deviation output (X-X’) and the previous deviation input X’

are opposite in sign (converging) in the differential (D) operation
The convergence differential time (Td2) is used as the differential time.

• When the integration reset (IRST) is "ON"

Yi

= 0 and IREM = 0 are output.

„

Format

Input

X

Output

Y

LIMIT, DB

Ki

Ts/Ti

I LIMIT

+

+

+

Kd

Td/Ts

+

+

+

Kp

Z

-1

Z

-1

-

Symbol: PID
Full Name: PID Control
Category: DDC
Icon: