1.7 DDC Instructions

1-137

1

Block Diagram

When the P + I + D offset reaches the upper or lower PID limit (UL, LL) or the PID

dead band (DB)
When the present P offset and the I offset are the same in sign (diverging), the I offset is
not renewed but is kept at the previous value. Oppositely, if the P and I offsets are oppo-
site in sign (converging towards 0), the I offset is renewed with the present value.

When the change in deviation output (X-X’) and the previous deviation input X’

are the same in sign (diverging) in the differential (D) operation
The divergence differential time (Td1) is used as the differential time.

When the change in deviation output (X-X’) and the previous deviation input X’

are opposite in sign (converging) in the differential (D) operation
The convergence differential time (Td2) is used as the differential time.

When the integration reset (IRST) is "ON"

Yi

= 0 and IREM = 0 are output.

„

Format

Input

X

Output

Y

LIMIT, DB

Ki

Ts/Ti

I LIMIT

+

+

+

Kd

Td/Ts

+

+

+

Kp

Z

-1

Z

-1

-

Symbol: PID
Full Name: PID Control
Category: DDC
Icon: