2 Standard System Function

2.2.3 Failure Trace Read Function (FTRC-RD)

2-26

Record Length

A Record is composed of the data for the selected items.
Word length of 1 record

= Bn × 1 word + Wn × 1 word + Ln × 2 words + Fn × 2 words

Bn: Number of bit type register selected points
Wn: Number of word type register selected points
Ln: Number of double-length integer type register selected points
Fn: Number of real number type register selected points
Maximum of record length

= 32 words (e.g. when there are 16 double-length integer type or

real number type registers)
Minimum of record length

= 1 words (e.g. when there is one bit type or integer type register)

Number of Records

The Number of Records is the following.

2.2.3 Failure Trace Read Function (FTRC-RD)

„

Outline

Reads the failure trace data and stores them in the user register. The data in the trace buffer
can be read out upon designating the number of records needed. Either the failure occur-
rence data or the restoration data are designated for readout. Enables the reset (initializa-
tion) of the failure trace buffer.

„

Format

Maximum Number of Records

32512/ Record Length

Number of records when the record length is the
maximum

0 to 1015

Number of records when the record length is the
minimum

0 to 32511

Symbol: FTRC-RD
Full Name: Failure-Trace Read
Category: SYSTEM
Icon: