2 Standard System Function

2.1.2 Receive Message Function (MSG-RCV)

2-18

When Non-procedural is set for Transmission Protocol

PARAM04 has no function. The settings of PARAM08, PARAM09, and PARAM10 are not
necessary. The message receivable register is only MW.

„

Input

EXECUTE (Receive Message Exection Command)

When the command becomes "ON", the message is receive. This must be held until COM-
PLETE (completion of process) or ERROR (occurrence of error) becomes "ON".

ABORT (Receive Message Forced Interruption Command)

This command forcibly interrupts the receiving of the message. This has priority over EXE-
CUTE (receive message execution command).

DEV-TYP (Transmission Device Type)

Designates transmission device type.

CPU Module

= 8, 215IF = 1, 217IF = 5, 218IF = 6, 218-02 = 16, SVB-01 = 11

PRO-TYP (Transmission Protocol)

Designates transmission protocol. In non-procedural transmission, a response is not sent to
the called station.

MEMOBUS : Setting

= 1

Non-procedural : Setting

= 2

CIR-NO (Circuit No.)

Designate the circuit No.

CPU Module

= 1, 2, 215IF = 1 to 8, 217IF = 1 to 24, 218IF = 1 to 8, SVB-01 = 1 to 16

CH-NO (Channel No.)

Designate the channel No. of the transmission unit. However, the channel number should be
set so as not to be duplicated on a single line.

CPU Module

= 1, 215IF = 1 to 13, 217IF = 1, 218IF = 1 to 10, SVB-01 = 1 to 8

PARAM (Setting Data Head Address)

The head address of the set data is designated. For details of the set data refer to "„ Param-
eter Details" (on page 2-14).