2 block write instruction (tblbw), Program example, Outline – Yaskawa MP900 Series Machine Controller New Ladder Editor User Manual

Page 178

Advertising
background image

1 Ladder Program Instructions

1.8.2 BLOCK WRITE Instruction (TBLBW)

1-168

„

Program Example

From the table defined as TABLE1, with DW00010 to DW00015 as a parameter table, data
(element type is integer type) from the starting table element position to the end position are
stored in block form in the area starting from MW00100.

1.8.2 BLOCK WRITE Instruction (TBLBW)

„

Outline

The TBLBW instruction writes the contents of a continuous region starting with the speci-
fied register (Write Data) to the file register table elements in block format that are specified
by table name (Table Name), row number, and column number. The data is processed
assuming that the type of the table elements in the storage destination register is the same as
that of the table elements in the storage source register.

If errors such as invalid table names, invalid row numbers, invalid column numbers, or
insufficient storage register data length are found, they are reported and the contents of the
storage destination register is retained without writing the data.

Upon normal termination, the number of words transferred is set in the [Output] and the
[Status] is turned OFF.

When an error occurs, the corresponding error code is set in the [Output] and the [Status] is
turned ON.

Table 1.33 Block Write Instruction Parameters

ADR

Type

Symbol

Name

Specifications

I/O

0

L

ROW1

Table element beginning
row number

Beginning row number of the target table
element (1 to 65535)

IN

2

L

COL1

Table element beginning
column number

Beginning column number of the target table
element (1 to 32767)

IN

4

W

RLEN

Number of row elements

Number of row elements (1 to 32767)

IN

5

W

CLEN

Number of column
elements

Number of column elements (1 to 32767)

IN

Advertising