1.7 DDC Instructions

1-135

1

1.7.6 PID CONTROL Instruction (PID)

„

Outline

The PID instruction executes a PID control operation according to the contents of a previ-
ously set parameter table. The input (Input) to the PID operation must be integer or real
number data.

Double-length integer data cannot be used. The configurations of the parameter tables for
integer and real number data are different. Operations are performed by processing each
parameter as an integer consisting of the lower-place 16 bits.

* Relay I/O Bit Assignment.

Table 1.16 Integer Type PID Instruction Parameters

ADR

Type

Symbol

Name

Specifications

I/O

0

W

RLY

Relay I/O

Relay input, relay output

IN/OUT

1

W

Kp

P gain

Gain of the P correction (a gain of 1 is set to 100)

IN

2

W

Ki

I gain

Gain of the integration circuit input (a gain of 1 is set
to 100)

IN

3

W

Kd

D gain

Gain of the differentiation circuit input (a gain of 1 is
set to 100)

IN

4

W

Ti

Integration time

Integration time (ms)

IN

5

W

Td1

Divergence differential
time

The differential time (ms) used in the case of diverg-
ing input.

IN

6

W

Td2

Convergence differential
time

The differential time (ms) used in the case of con-
verging input.

IN

7

W

IUL

Upper integration limit

Upper limit for the I correction value

IN

8

W

ILL

Lower integration limit

Lower limit for the I correction value

IN

9

W

UL

Upper PID limit

Upper limit for the P + I + D offset

IN

10

W

LL

Lower PID limit

Lower limit for the P + I + D offset

IN

11

W

DB

PID output dead band

Width of the dead band for the P + I + D offset

IN

12

W

Y

PID output

PID offset output (also output to the A register)

OUT

13

W

Ti

I offset

I offset stored

OUT

14

W

IREM

I remainder

I remainder stored

OUT

15

W

X

Input value storage

Present deviation input value stored

OUT

BIT

Symbol

Name

Specifications

I/O

0

IRST

Integration reset

"ON" is input when integration is reset.

IN

1 to 7

(Reserved)

Reserved relay for input

IN

8 to F

(Reserved)

Reserved relay for output

OUT