Parameter – Yaskawa MP900 Series Machine Controller New Ladder Editor User Manual

Page 233

Advertising
background image

2 Standard System Function

2.3.2 Inverter Constant Read Function (ICNS-RD)

2-40

„

Parameter

Note: In the case of an inverter response error, the error codes from the

inverter are indicated in bit0 to bit7.
01H(1): function code error
02H(2): reference No. error
Numbers in ( ) are of decimal expressions.

I/O

Definition

Parameter

Name

I/O

Designation

Setting

Input

Execute

B-VAL

Inverter constant read execution instruction

Abort

B-VAL

Inverter constant read forced interruption instruction

Dev-Typ

I-REG

Type of transmission device

215IF

= 1

MP930

= 4

SVB-01

= 11

Cir-No

I-REG

Line No.

215IF

= 1, 2

MP930

= 1

SVB-01

= 1 to 16

St-No

I-REG

Slave station No.

215IF

= 1 to 64

MP930

= 1 to 14

SVB-01

= 1 to 14

Ch-No

I-REG

Transmission buffer channel No.

215IF

= 1 to 3

MP930

= 1

SVB-01

= 1 to 8

Cns-Typ

I-REG

Type of inverter constant
0

= direct designation of reference No. 1 = An. 2 = Bn, 3 = Cn,

4

= Dn, 5 = En, 6 = Fn, 7 = Hn, 8 = Ln, 9 = On, 10 = Tn

Cns-No

I-REG

Inverter constant No. (1 to 99)
The upper limit will differ according to the type of inverter.
If Cns-Typ

= 0, designate the reference No.

Cns-Size

I-REG

Number of inverter constants (number of data to be read) 1 to 100

Dat-Adr

Address in-
put

Register address of read-out destination (address of MW or DW)

Output

Busy

B-VAL

Inverter constants are being read.

Complete

B-VAL

The reading of inverter constants has been completed.

Error

B-VAL

Occurrence of error

Status

I-REG

Inverter constant read execution status

Table 2.16 Configuration of Inverter Constant Read Execution Status (STASTUS)

Name

Bit No.

Remarks

System reserved

bit0 to bit7

Execution sequence error

bit8

The function will not be executed.

Transmission parameter
error

bit9

The function will not be executed.

Designated type error

bit10

The function will not be executed.

Designated No. error

bit11

The function will not be executed.

Error in number (amount)
of the designated data

bit12

The function will not be executed.

Transmission error

bit13

The function will not be executed.

Inverter response error

bit14

The function will not be executed.

Address input error

bit15

The function will not be executed.