Device Profile

C.2

Analog Input Point Object (0x0A)

Table C-1

Analog Input Point Object (0x0A) – Instance 1 (mass flow)

Attrib
ID

Name

Data type

Service

Mem

Description

Comments

3

Value

REAL

Get

V

Current value of mass
flow process variable

Based on Attribute 8

4

Status

BOOL

Get

V

Point status

• 0 = Good
• 1 = Alarm state

8

Value data type

USINT

Get

V

Data type used to report
mass flow process
variable

• 1 = REAL

100

Process total

REAL

Get
Reset

(1)

(1) Service code 0x4B.

V

Current value of mass
total

101

Inventory total

REAL

Get
Reset

(2)

(2) Service code 0x4C.

V

Current value of mass
inventory

102

Value
engineering
units

UINT

Set

NV

Mass flow measurement
unit

See Table 6-2 for unit
codes.

103

Total
engineering
units

UINT

Get

V

Mass total and inventory
units

Transmitter
automatically
determines this based
on Attribute 102.
See Table C-12 for unit
codes.

104

Damping

REAL

Set

NV

Flow damping value

• Unit = seconds
• Applied to both mass

flow and liquid volume
flow

105

Cutoff

REAL

Set

NV

Value below which mass
flow will be reported as 0

106

Meter factor

REAL

Set

NV

A multiplier to the
calculated mass flow

107

Flow direction

USINT

Set

NV

Determines how flow
direction affects reported
flow rate and flow totals

• 0 = Forward only
• 1 = Reverse only
• 2 = Bidirectional
• 3 = Absolute value
• 4 = Negate/forward

only

• 5 = Negate/

bidirectional

108

Reset mass total USINT

Set

V

Resets the mass total

• 1 = Reset

109

Reset mass
inventory

USINT

Set

V

Resets the mass
inventory

• 1 = Reset