C-2, c-3, D c-3, See table c-2 – Emerson Process Management MICRO MOTION 2400S User Manual

Page 153: Instance 3 (density) – see table c-3

Advertising
background image

Configuration and Use Manual

145

Device Profile

D

e

vice Pr

ofile

In

de
x

Displa

y Codes

Men

u

s

Table C-2

Analog Input Point Object (0x0A) – Instance 2 (liquid volume flow)

Attrib
ID

Name

Data type

Service

Mem

Description

Comments

3

Value

REAL

Get

V

Current value of liquid
volume flow process
variable

Based on Attribute 8

4

Status

BOOL

Get

V

Point status

• 0 = Good
• 1 = Alarm state

8

Value data type

USINT

Get

V

Data type used to report
volume flow process
variable

1 (REAL)

100

Process total

REAL

Get
Reset

(1)

(1) Service code 0x4B.

V

Current value of liquid
volume total

101

Inventory total

REAL

Get
Reset

(2)

(2) Service code 0x4C.

V

Current value of liquid
volume inventory

102

Value
engineering
units

UINT

Set

NV

Liquid volume flow
measurement unit

See Table 6-3 for unit
codes.

103

Total
engineering
units

UINT

Get

V

Liquid volume total and
inventory units

Transmitter
automatically
determines this based
on Attribute 102.
See Table C-13 for unit
codes.

105

Cutoff

REAL

Set

NV

Value below which liquid
volume flow will be
reported as 0

106

Meter factor

REAL

Set

NV

A multiplier to the
calculated liquid volume
flow

108

Reset volume
total

USINT

Set

V

Resets the volume total

• 1 = Reset

109

Reset volume
inventory

USINT

Set

V

Resets the volume
inventory

• 1 = Reset

Table C-3

Analog Input Point Object (0x0A) – Instance 3 (density)

Attrib
ID

Name

Data type

Service

Mem

Description

Comments

3

Value

REAL

Get

V

Current value of density
process variable

Based on Attribute 8

4

Status

BOOL

Get

V

Point status

• 0 = Good
• 1 = Alarm state

8

Value data type

USINT

Get

V

Data type used to report
density process variable

1 (REAL)

102

Value
engineering
units

UINT

Set

NV

Density measurement unit See Table 6-5 for unit

codes.