C.8 api object (0x69), Api object (0x69), L, see table c-10 – Emerson Process Management MICRO MOTION 2400S User Manual

Page 170: See table c-10

Advertising
background image

162

Micro Motion

®

Model 2400S Transmitters for DeviceNet

Device Profile

C.8

API Object (0x69)

26

Enable offline
password

BOOL

Set

NV

Enable or disable the
password requirement to
access the offline menu

• 0 = Disabled
• 1 = Enabled

27

Offline password

UINT

Set

NV

The offline password for
entering the offline menu

0–9999

28

Update period

UINT

Set

NV

The period in which the
display is updated

Unit = milliseconds

29

Process variable
index

USINT

Set

V

The process variable in
which the precision will be
set in Attribute 30

See Table C-15 for
codes.

30

Process variable
precision

USINT

Set

NV

The number of digits
displayed to the right of
the decimal point for the
process variable selected
with Attribute 29

0–5

31

Language

USINT

Set

NV

Display language
selection

• 0 = English
• 1 = German
• 2 = French
• 3 = Katakana

(1)

• 4 = Spanish

32

Enable IrDA port

USINT

Set

NV

Enable or disable the
IrDA port

• 0 = Disabled
• 1 = Enabled

(1) Not available in this release.

Table C-10

API Object (0x69) – Instance 1

Attrib
ID

Name

Data type

Service

Mem

Description

Comments

1

Temperature
corrected
density

REAL

Get

V

Current value

2

Temperature
corrected
(standard)
volume flow

REAL

Get

V

Current value

3

Temperature
corrected
(standard)
volume total

REAL

Get
Reset

(1)

V

Current value

4

Temperature
corrected
(standard)
volume
inventory

REAL

Get
Reset

(2)

V

Current value

5

Batch weighted
average density

REAL

Get

V

Current value

6

Batch weighted
average
temperature

REAL

Get

V

Current value

Table C-9

Local Display Object (0x68) – Instance 1 continued

Attrib
ID

Name

Data type

Service

Mem

Description

Comments

Advertising