Emerson Process Management MICRO MOTION 2400S User Manual

Page 60

Advertising
background image

52

Micro Motion

®

Model 2400S Transmitters for DeviceNet

Using the Transmitter

Reset all inventories

Analog Input Point Object (0x0A)
Instance: 0
Attribute ID: 102
Service: Set
Value: 1

Reset mass totalizer

Analog Input Point Object (0x0A)
Instance: 1
Service: Reset Total (0x32)

Reset mass inventory

Analog Input Point Object (0x0A)
Instance: 1
Service: Reset Inventory (0x33)

Reset liquid volume totalizer

Analog Input Point Object (0x0A)
Instance: 2
Service: Reset Total (0x32)

Reset liquid volume inventory

Analog Input Point Object (0x0A)
Instance: 2
Service: Reset Inventory (0x33)

Reset gas standard volume totalizer

Gas Standard Volume Object (0x64)
Instance: 1
Service: Reset Total (0x4B)

Reset gas standard volume inventory

Gas Standard Volume Object (0x64)
Instance: 1
Service: Reset Inventory (0x4C)

Reset API reference volume total

API Object (0x69)
Instance: 1
Service: Reset Total (0x4B)

Reset API reference volume inventory

API Object (0x69)
Instance: 1
Service: Reset Inventory (0x4C)

Reset ED standard volume total

Enhanced Density Object (0x6A)
Instance: 1
Service: Reset Total (0x4B)

Reset ED net mass total

Enhanced Density Object (0x6A)
Instance: 1
Service: Reset Total (0x4C)

Reset ED net volume total

Enhanced Density Object (0x6A)
Instance: 1
Service: Reset Total (0x4D)

Reset ED standard volume inventory

Enhanced Density Object (0x6A)
Instance: 1
Service: Reset Inventory (0x4F)

Reset ED net mass inventory

Enhanced Density Object (0x6A)
Instance: 1
Service: Reset Inventory (0x50)

Reset ED net volume inventory

Enhanced Density Object (0x6A)
Instance: 1
Service: Reset Inventory (0x51)

Table 7-8

Totalizer and inventory control with a DeviceNet tool using explicit write continued