66

Micro Motion

®

Model 2400S Transmitters for DeviceNet

Optional Configuration

Some alarms can be reclassified. For example:

The default severity level for Alarm A020 (calibration factors unentered) is

Fault

, but you can

reconfigure it to either

Informational

or

Ignore

.

The default severity level for Alarm A102 (drive over-range) is

Informational

, but you can

reconfigure it to either

Ignore

or

Fault

.

For a list of all status alarms and default severity levels, see Table 8-8. (For more information on
status alarms, including possible causes and troubleshooting suggestions, see Table 11-2.)

To configure alarm severity:

Using ProLink II, see Figure B-3.

Using a DeviceNet tool, refer to Table C-7 and:

a.

Set the alarm index (Attribute 18).

b.

Set the severity for that alarm (Attribute 19).

Note: This functionality is not available via the display menus.

Table 8-8

Status alarms and severity levels

Alarm code

ProLink II message

Default
severity

Configurable?

Affected by
fault timeout?

A001

(E)EPROM Checksum Error (CP)

Fault

No

No

A002

RAM Error (CP)

Fault

No

No

A003

Sensor Failure

Fault

Yes

Yes

A004

Temperature Sensor Failure

Fault

No

Yes

A005

Input Overrange

Fault

Yes

Yes

A006

Not Configured

Fault

Yes

No

A008

Density Overrange

Fault

Yes

Yes

A009

Transmitter Initializing/Warming Up

Ignore

Yes

No

A010

Calibration Failure

Fault

No

No

A011

Zero Too Low

Fault

Yes

No

A012

Zero Too High

Fault

Yes

No

A013

Zero Too Noisy

Fault

Yes

No

A014

Transmitter Failed

Fault

No

No

A016

Line RTD Temperature Out-of-Range

Fault

Yes

Yes

A017

Meter RTD Temperature Out-of-Range

Fault

Yes

Yes

A020

Calibration Factors Unentered (FlowCal)

Fault

Yes

No

A021

Incorrect Sensor Type (K1)

Fault

No

No

A029

PIC/Daughterboard Communication Failure

Fault

No

No

A030

Incorrect Board Type

Fault

No

No

A031

Low Power

Fault

No

No

A032

Meter Verification/Outputs In Fault

Fault

No

No

A033

Sensor OK, Tubes Stopped by Process

Fault

Yes

Yes

A102

Drive Overrange/Partially Full Tube

Info

Yes

No

A104

Calibration in Progress

Info

Yes

(1)

No

A105

Slug Flow

Info

Yes

No

A107

Power Reset Occurred

Info

Yes

No