Read/write image data

Overview

J

Please also observe the relevant description of possible

image data provided in the EZ800 manual, the EZD

manual, or in the EZSoft Help.
The latest editions of these manuals are available as PDF

files from the Internet at:

www.EatonElectrical.com.

EZ800

manual search term: MN05013004E. EZD manual search

term: MN05013005E.
The information provided in Section “General notes on

working with image data” on Page 49 also applies to

EZ800/EZD.

Operands

Meaning

Read/write

Command

Page

IW0

Read local inputs IW0

Read

01

100

IW1 – IW8

Read inputs of the stations IW1 to IW8

Read

01

102

IA1 – IA4

Read local analog inputs IA1 to IA4

Read

02

103

ID1 – ID16

Read local diagnostics ID1 to ID16

Read

03

105

QW0,

QW1 – QW8

Read and write local QW0 outputs/outputs

of the stations QW1 to QW8

Read/write

04

107

QA1

Reading and writing local analog output

QA1

Read/write

05

109

P1 – P4

Reading local P buttons

Read

06

110

R1 – R16

S1 – S8

Reading RW.. inputs/SW.. outputs from

EZ-LINK

Read

07/09

112

RN1 – RN32

SN1 – SN32

Reading receive data network RN1 ..

RN32/send data network SN1 .. SN32

Read

08/0A

114

M...

Reading and writing markers

Read/write

0B – 0E

116