Inputs/Outputs, EZ700/800/EZD Operating Mode

MN05013001E

36

“Inputs 3 bytes” module:
operating mode, S1 – S8

The normal PROFIBUS-DP master data exchange with the

EZ204-DP slave is via input data bytes 0, 1, 2.

Requirement:

The “Inputs, 3 bytes” module must have been selected.

The master reads bytes 0, 1, 2 for the following data:

Table 1:

Byte 0: Operating mode

Example:

Byte

Meaning

Value

0

Scan the operating mode

J

Table 1

1

Scan status of the EZ outputs S1 to

S8

J

Table 2

2

Not assigned

00

hex

J

The output data and control commands can now only be

used if you have selected the appropriate modules as well.

EZ/EZD operating mode

Bit

7

6

5

4

3

2

1

0

Stop/Run

with debounce

0

0

0

1

0

0

0

0/1

without debounce

0

0

1

0

0

0

0

0/1

Value 21

hex

EZ/EZD is in Run mode and is working with input

debounce.