Read/write function block data – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 127

Advertising
background image

Read/write function block data

For more information visit: www.EatonElectrical.com

MN05013001E

123

Table 52: Operand overview

Table 53: Index 0: Bit IO

Table 54: Index 1 - Mode

Index
(hex)

Operand

Read

Write

00

Bit IO, J Table 53

×

01

Mode, J Table 54

×

02

Comparison value 1

I1

×

c

1

03

Gain factor for I1 (I1 = F1 χ value)

F1

×

c

1

04

Comparison value 2

I2

×

c

1

05

Gain factor for I2 (I2 = F2 χ value)

F2

×

c

1

06

Offset for value I1

OS

×

c

1

07

Switching hysteresis for value I2 (the value of HY

is for both positive and negative hysteresis.)

HY

×

c

1

1) The value can only be written if it is assigned to a constant in the program.

J

The data for index 2 to 7 is transferred as a 32-bit value in

Intel format (Data 1 – Low Byte to Data 4 – High Byte).

Bit 7 6 5 4 3 2 1

0

FB output Data 3

– – – – – – CY

1

Q1

2

1) Status 1 if the value range is exceeded
2) Status 1 if the condition is fulfilled (e.g. I1 < I2 with LT mode)

Data 1
(hex)

00

LT

Less than (I1 < I2)

01

EQ

Equal to (I1 = IGT)

02

GT

Greater than (I1 > I2)