Ez800/ezd control commands – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 108

Advertising
background image

For more information visit: www.EatonElectrical.com

EZ800/EZD Control Commands

MN05013001E

104

Example

A voltage signal is present at analog input 1. The required

telegrams for reading the analog value are as follows:

Byte 5 – Data 1 (Low Byte): D9

hex

Byte 6 – Data 2 (High Byte): 02

hex

J

corresponding 16-bit value: 02D9

hex

= 729 (7.29 V)

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

81

80

1

Command: Read

91

Response: Read

successful

C2

2

Len

02

02

3

Type

02

02

4 Index

01

1

01

1

5

Data 1

00

D9

6

Data 2

00

02

7

Data 3

00

00

8

Data 4

00

00

1) 01 = Analog input 1