Inputs/Outputs, EZ700/800/EZD Operating Mode

MN05013001E

38

“Inputs 1 byte” module: S1 –

S8

When this module is selected, the master only receives 1 byte

(coil output data S1 to S8) via PROFIBUS.

Requirement:

The “Inputs, 1 byte” module must have been selected.

“Outputs 3 bytes” module:
operating mode, R9 – R16,
R1 – R8

The normal PROFIBUS-DP master data exchange with the

EZ204-DP slave is provided with output data bytes 0, 1, 2.

Requirement:

The “Outputs; 3 bytes” module must have been selected.

The master reads bytes 0, 1, 2 for the following data:

Byte

Meaning

Value

0

Scan status of the EZ

outputs S1 to S8

J

Table 2 on Page 37

J

The output data and control commands can now only be

used if you have selected the appropriate modules as well.

Byte

Meaning

Value

0

Set operating mode

J

Table 3

1

Set/reset the EZ/EZD inputs R9 to

R16

J

Table 4

2

Set/reset the EZ/EZD inputs R1 to

R8

J

Table 5

J

The output data and control commands can now only be

used if you have selected the appropriate modules as well.