Control commands for EZ700

MN05013001E

56

Local analog inputs: IA1 – IA4
The analog inputs on the EZ700 basic unit (I7, I8, I11, I12) can

be read directly via PROFIBUS-DP. The 16-bit value is

transferred in Intel format (Low Byte first).
Telegram structure

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 44

1

Command: Read

88

Response:

Read successful

C2

Command

rejected

C0

1

2

Len

02

02

3

Type

8C

8C

4

Index

00 – 03

2

00 – 03

2

5

Data 1 (Low Byte)

00

J

Table 14

6

Data 2 (High Byte)

00

J

Table 14

7 – 8

Data 3 – 4

00

00

1) Possible causes J page 91
2) 00 = Analog input I7

01 = Analog input I8

02 = Analog input I11

03 = Analog input I12