Read/write image data

For more information visit: www.EatonElectrical.com

MN05013001E

57

Example:

A voltage signal is present at analog input 1. The required

telegrams for reading the analog value are as follows:

Table 14: Example telegram for reading the value at the analog

input

Byte 5 – Data 1 (Low Byte): 4B

hex

Byte 6 – Data 2 (High Byte): 03

hex

J

corresponding 16-bit value: 034B

hex

= 843

The value 843 corresponds to the IO bit value of the analog

converter. The following conversion is required for the actual

analog value:

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 44

1

Command: Read

88

Response:

Read successful

C2

2

Len

02

02

3

Type

8C

8C

4

Index

02

1

02

1

5 Data

1

00

4B

6 Data

2

00

03

7 Data

3

00

00

8

Data 4

00

00

1) 02 = Analog input I11

10 V

×

IO bit value =>

10 V

×

843 = 8.24 V

1023

1023