Connecting PROFIBUS-DP

For more information visit: www.EatonElectrical.com

MN05013001E

19

Connecting PROFIBUS-DP

Use a 9-pole SUB-D plug to connect the PROFIBUS-DP

interface to the PROFIBUS-DP fieldbus. For this use the

special PROFIBUS-DP plug and the special PROFIBUS-DP

cable available from the Eaton range of accessories. The type

of cable used determines the permissible maximum bus

length and the transfer rate.

PROFIBUS-DP connection
assignment

Connections 3, 8 and the shield are sufficient for data transfer.

Pin

Signal name

Designation

1

Not assigned

-

2

Not assigned

-

3

RxD/TxD-P (B Line)

Receive/Send data P

4

CNTR-P / RTS

Request to Send

5

DGND

Data reference potential

6

VP

+5V DC for external bus connection

7

Not assigned

-

8

RxD/TxD-N (A-

Line)

Receive/Send data N

9

Not assigned

-

6

7

8

9

2

3

4

5

1

4

3

8

5

6

CNTR-P

RxD/TxD-P (B/B')

RxD/TxD-N (A/A')

DGND

VP