Control commands for ez700 – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 82

Advertising
background image

For more information visit: www.EatonElectrical.com

Control commands for EZ700

MN05013001E

78

Table 29: Index 01 – Control byte

Example:

the actual value of C3 is to be read:

Explanation:
Data 1 = 12

Data 2 = 03
l

resulting 16-bit value = 0312

hex

= 786

dec

Counter status = 786

Data 1

Bit 7

6

5

4

3

2

1

0

FB output

C

4

RE

3

D

2

Q1

1

1) Switch contact
2) Count direction: 0 = up counting,

1 = down counting

3) Reset, the timing relay is reset (reset coil)
4) Count coil, counts on every rising edge

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Command: Read

89

Response: Read successful

C2

1

Type

8F

8F

2

Instance

02

02

3

Index

02

02

4

Data1

00

12

5

Data 2

00

03

6

Data 3

00

00

7

Data 4

00

00