EZ800/EZD Control Commands

MN05013001E

94

Byte 0 – Toggle byte

Byte 0 is used to activate the sending of a control command

with the toggle function.

Procedure
X

To send a command, bit 7 must be toggled, i.e. set either

from 1 to 0 or from 0 to 1.

X

Then poll the toggle bit for the coupling modules response

until it has the same status as the toggle bit sent. This status

indicates to the master that the response to the sent

command is valid.

X

Do not send a new command until you have received a

response (changing of the toggle bit), otherwise the

response of the previous command will be overwritten

before it can be read.

The following tables show the different control commands

possible. These essential control commands fall into three

essential categories – real-time clock, image and function

blocks.

Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8

Bit

7

6

5

4

3

2

1

0

01

hex

/861

hex

0/1

0

0

0

0

0

0

1

Toggle bit

fixed

J

In order to use input/output data and control commands

simultaneously:
Only after the “Control commands” data exchange has

been completed, will the I/O data be refreshed.
All specified commands and parameters must be

transferred in hexadecimal format.