Local p buttons: p1 - p4, Local p buttons: p1 – p4, Read/write image data – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 67

Advertising
background image

Read/write image data

For more information visit: www.EatonElectrical.com

MN05013001E

63

Local P buttons: P1 – P4
The local P buttons are the display cursor buttons of the

EZ700 basic unit. You can scan the buttons in both RUN and

STOP mode.

Only one byte has to be transferred for the P buttons.
Telegram structure

J

Ensure that the P buttons are also activated via the System

menu (in the basic unit).

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 44

1

Command: Read

88

Response:

Read successful

C2

Command

rejected

C0

1

2

Len

01

01

3

Type

8A

8A

4

Index

00

00

5

Data 1 (Low Byte)

00

J

Table 17

6 – 8

Data 2 – 4

00

00

1) Possible causes J page 91