Local outputs: q1 - q8, Local outputs: q1 – q8, Read/write image data – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 69

Advertising
background image

Read/write image data

For more information visit: www.EatonElectrical.com

MN05013001E

65

Local outputs: Q1 – Q8
The local outputs can be read directly via the PROFIBUS-DP

fieldbus.
Telegram structure

Table 18: Byte 5: Data 1

Example:

Data 1 = 52

hex

J

Q2, Q5 and Q7 are active.

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 44

1

Command: Read

88

Response:

Read successful

C2

Command

rejected

C0

1)

2

Len

01

01

3

Type

85

85

4

Index

00

00

5

Data 1 (Low Byte)

00

J

Table 18

6 – 8

Data 2 – 4

00

00

1) Possible causes J page 91

Data 1 Bit 7

6

5

4

3

2

1

0

Q1

0/1

Q2

0/1

..

..

Q8

0/1