EZ800/EZD Control Commands

MN05013001E

102

Read inputs of the stations IW1 to IW8
The EZ800 and EZD devices can be remotely expanded very

simply using the EZ-NET. The service offered here makes it

possible to implement read access to the inputs of individual

NET stations.
Telegram structure

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 94

1

Command: Read

91

Response:

Read successful

C2

Command

rejected

C0

2

Len

02

02

3

Type

01

01

4

Index

01 – 08

1

01 – 08

1

5

Data 1 (Low Byte)

00

J

Table 45

on Page 100.

6

Data 2 (High Byte)

00

7 – 8

Data 3 – 4

00

00

1) Corresponds to address of network station