Appendix, What happens if – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 185

Advertising
background image

For more information visit: www.EatonElectrical.com

181

MN05013001E

Appendix

What Happens If ...?

Event

Explanation

Remedy

POW LED not lit

No power supply

Connect and switch on power

supply

POW LED flashing

Data transfer via EZ-LINK OK

BUS LED not lit

No PROFIBUS-DP data

communication

Connect and start

PROFIBUS-DP

BUS LED lit

Data transfer via PROFIBUS-

DP OK

Slave not signalling

– No slave address set

– No bus terminating resistor

present

– Cable, plug faulty

– No power supply

– Set slave address

– Set bus terminating resistors

– Check connection

– Provide power supply to

device

Write command rejected

– Command not permissible

– EZ display not on the Status

display

– Change command

– Show Status display

Actual value is zero

No actual value present

Function relay does not have an

actual value or not triggered