Read/write date and time

For more information visit: www.EatonElectrical.com

MN05013001E

95

Read/write date and time

Telegram structure

J

Please also note the relevant description of the real-time

clock provided in the EZ800 manual and the EZD manual.
The latest edition of these manuals are available as PDF

files from the Internet at:

www.EatonElectrical.com.

EZ800

manual search term: MN05013004E. EZD manual search

term: MN05013005E.

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 94

1

Command

Read

93

Write

B3

Response

Read

successful

C2

Write

successful

C1

Command

rejected

C0

2

Len

05

05

3

Index

00

00

4 – 8

Data 1 – 5

Read operation

00

J

Table 43

For write

operation

J

Table 43