Read/write function block data

For more information visit: www.EatonElectrical.com

MN05013001E

133

Table 67: Operand overview

Table 68: Index 0: Bit IO

Index
(hex)

Operand

Value

Read

Write

00

Bit IO

J

Table 68

×

01

Mode/Parameter

02

Upper setpoint

SH

In integer range from

2147483648 to

+2147483647

×

c

1

03

Lower setpoint

SL

×

c

1

04

Preset actual value

SV

×

c

1

05

Actual value in Run mode

QV

×

1) The value can only be written if it is assigned to a constant in the program.

J

The data for index 2 to 5 is transferred as a 32-bit value in

Intel format (Data 1 – Low Byte to Data 4 – High Byte).

Bit 7 6 5 4 3

2

1

0

FB input Data 1

– – – – SE

1

D

2

C

3

RE

4

FB output Data 3

– – – – ZE

5

CY

6

FB

7

OF

8

1) Transfer preset actual value on rising edge
2) Count direction: 0 = up counting, 1 = down counting
3) Count coil, counts on every rising edge
4) Reset actual value to zero
5) Zero: Status 1 if the value of the function block output QV (the

counter status) equals zero

6) Carry: Status 1 if the value range is exceeded
7) Fall below: Status 1 if the actual value lower setpoint
8) Overflow: Status 1 if the actual value upper setpoint