Control commands for ez700 – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 94

Advertising
background image

For more information visit: www.EatonElectrical.com

Control commands for EZ700

MN05013001E

90

Table 40: Index 00 – Parameters

Example:

Data 1 (Byte 5) = 0x03
Meaning:

The values of the WH.. 7-day time switch from channel A and

B appear in the parameter menu.

Table 41: Index 01 – Control byte

Channel A, Index 11/12/13

Index 0x11 channel A Weekday on/off

Data 1 (Byte 5) – Weekday on

Data 2 (Byte 6) – Weekday off

0x01 = Sunday ... 0x07 = Saturday
The 16-bit value equals 0x00 if the channel is not used.
Index 0x12 – On time (2 Byte)

Index 0x13 – Off time (2 Byte)

Data 1 (Byte 5) – Hour

Data 2 (Byte 6) – Minute
Example: On time at 13:43 p.m.

Data 1 = 0x0D

Data 2 = 0x2B

Meaning

Bit 7

6

5

4

3

2

1

0

Appears in the parameter menu

Channel A

0/1

Channel B

0/1

Channel C

0/1

Channel D

0/1

Unused bits

Data 1

Bit 7

6

5

4

3

2

1

0

FB output

Q1

1

1) Status 1, if the count condition is fulfilled.

Advertising