Markers: m1 - m16/n1 - n16, Markers: m1 – m16/n1 – n16, Control commands for ez700 – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 64

Advertising
background image

For more information visit: www.EatonElectrical.com

Control commands for EZ700

MN05013001E

60

Markers: M1 – M16/N1 – N16
Unlike the write operation, the marker read operation reads

the entire marker area of a particular marker type (M or N) is

read.
Telegram structure

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 44

1

Command: Read

88

Response:

Read successful

C2

Command

rejected

C0

1

2

Len

01

01

3

Type

M marker

86

86

N marker

87

87

4

Index

2

00

00

5

Data 1 (Low Byte)

00

J

Table 15

6

Data 2 (Low Byte)

00

J

Table 15

7 – 8

Data 3 – 4

00

00

1) Possible causes J page 91
2) There are 16 M markers and 16 N markers. The markers are

addressed by Type and Index:

Use Type to select the M or N marker.

Use Index to select the marker number.