Ez800/ezd control commands – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 160

Advertising
background image

For more information visit: www.EatonElectrical.com

EZ800/EZD Control Commands

MN05013001E

156

Example

The channel A parameters of 7-day time switch HW19 are to

be read.

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

81

80

1

Command: Read

92

Response: Read

successful

C2

2

Type

1C

1C

3

Instance

13

13

4 Index

02

02

5

Data 1

00

62

6

Data 2

00

0B

7

Data 3

00

7B

8

Data 4

00

25

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Date 2 = 0B

hex

Date 1 = 62

hex

ON

0

0

0

0

1

0

1

1

0

1

1

0

0

0

1

0

Weekday

Hour

Minute

Switch-on time:

Weekday = 01

hex

.. Monday

Hour = 0D

hex

.. 1300 hours

Minute = 22

hex

.. 34 minutes

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Date 4 = 25

hex

Date 3 = 7B

hex

OFF

0

0

1

0

0

1

0

1

0

1

1

1

1

0

1

1

Weekday

Hour

Minute

Switch-off time:

Weekday = 04

hex

.. Thursday

Hour = 15

hex

.. 2100 hours

Minute = 59

hex

.. 34 minutes