Read/write function block data

For more information visit: www.EatonElectrical.com

MN05013001E

127

Table 58: Operand overview

Table 59: Index 0 – Bit IO

Table 60: Index 1 - Mode

Index
(hex)

Operand

Read

Write

00

Bit IO, J Table 59

×

01

Mode, J Table 60

×

02

Source range 1

I1

×

c

1

03

Target range 2

I2

×

c

1

04

Number of elements to

compare: 8 (max. 192 bytes)

NO

×

c

1

1) The value can only be written if it is assigned to a constant in the

program.

J

The data for index 2 to 4 is transferred as a 32-bit value in

Intel format (Data 1 – Low Byte to Data 4 – High Byte).

Bit 7 6 5 4 3

2

1

0

FB input Data 1

– – – – –

EN

1

FB output Data 3

– – – – EQ

2

E3

3

E2

4

E1

5

1) Activates the function block on status 1.
2) Status 1 if the data ranges are equal; status 0 if not equal

Error outputs

3) Status 1 if the number of elements exceeds the source or target

range.

4) Status 1 if the source and target range overlap.
5) Status 1 if the source or target range are outside of the available

marker range (offset error)

Mode

Data 1 (hex)

Operating mode

02

Compare (internal EZ status signal

for Block Compare mode)