Read/write function block data

For more information visit: www.EatonElectrical.com

MN05013001E

125

Table 55: Operand overview

Table 56: Index 0: Bit IO

Table 57: Index 1 - Mode

Index
(hex)

Operand

Read

Write

00

Bit IO, J Table 56

×

01

Mode, J Table 57

×

02

First operand

I1

×

c

1

03

Second operand

I2

×

c

1

04

Result

QV

×

1) The value can only be written if it is assigned to a constant in

the program.

J

The data for index 2 to 4 is transferred as a 32-bit value in

Intel format (Data 1 – Low Byte to Data 4 – High Byte).

Bit

7 6 5 4 3 2

1

FB output Data 3

– – – – – ZE

1

CY

1

1) Status 1 if the value of the function block output QV (the

calculation result) equals zero

2) Status 1 if the value range is exceeded

Data 1
(hex)

00

ADD

Add (I1 + I2 = QV)

01

SUB

Subtract (I1 – I2 = QV)

02

MUL

Multiply (I1 × I2 = QV)

03

DIV

Divide (I1 : I2 = QV)