Text function blocks: d1 - d16, Text function blocks: d1 – d16, Read/write image data – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 57

Advertising
background image

Read/write image data

For more information visit: www.EatonElectrical.com

MN05013001E

53

Text function blocks: D1 – D16
The following commands are used to read the logic state of

the individual text function blocks (D markers).
Telegram structure

Table 12: Byte 5 to 6: Data 1 to 2

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 44

1

Command: Read

88

Response:

Read successful

C2

Command

rejected

C0

1

2

Len

01

01

3

Type

94

94

4

Index

00

00

5

Data 1 (Low Byte)

00

J

Table 12

6

Data 2 (High Byte)

00

J

Table 12

7 – 8

Data 3 – 4

00

00

1) Possible causes J page 91

Data 1 Bit 7

6

5

4

3

2

1

0

D1

0/1

D2

0/1

...

...

D8

0/1

Data 2 Bit 7

6

5

4

3

2

1

0

D9

0/1

D10

0/1

...

...

D16

0/1

Advertising