Read/write function block data – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 79

Advertising
background image

Read/write function block data

For more information visit: www.EatonElectrical.com

MN05013001E

75

Table 25: Index 00 – Parameters

Example:

Data 1 (Byte 5) = 0xA3, Data 2 (Byte 6) = 0x03
l

Resulting 16-bit value = 03A3

hex

Meaning: HY, OS, F2, F1 are assigned a constant; I1, I2 are

assigned to a variable such as I7, I8 C2...etc., appears in the

Parameter menu;
The output of the analog value comparator is active for as long

as the comparison (I1

×

F1) + OS = (I2

×

F2) + HY is fulfilled.

Table 26: Index 01 – Control byte

Meaning

Bit 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Appears in the parameter menu
Yes/no

0/1

Compare
FB not used

0

0

0

EQ (=)

0

0

1

GE ( )

0

1

0

LE ( )

0

1

1

GT (>)

1

0

0

LT (<)

1

0

1

Use as constant and therefore can be written to
I1= Constant

0/1

F1= Constant

0/1

I2= Constant

0/1

F2 = Constant

0/1

OS = Constant

0/1

HY = Constant

0/1

Not used

0 0 0 0 0 0

Bit 7 6 5 4 3

2

1

0

FB output Data 3

– – – – –

Q1

1

1) Status 1 if comparison condition is fulfilled.