Read/write image data – Eaton Electrical PROFIBUS-DP EZ204-DP User Manual

Page 65

Advertising
background image

Read/write image data

For more information visit: www.EatonElectrical.com

MN05013001E

61

Table 15: Byte 5 to 6: Data 1 to 2

Example:

The N markers are read:

The markers N3, N11 and N16 are set.

Data 1

Bit 7

6

5

4

3

2

1

0

M

N

M1

N1

0/1

M2

N2

0/1

...

...

...

M8

N8

0/1

Data 2

Bit 7

6

5

4

3

2

1

0

M9

N9

0/1

M10

N10

0/1

...

...

M16

N16

0/1

Byte

Meaning

Value (hex), sent by
Master

Slave

0

Toggle byte

J

page 44

1

Command: Read

88

Response:

Read successful

C2

Command

rejected

C0

1

2

Len

01

01

3

Type

N marker

87

87

4

Index

00

00

5

Data 1 (Low Byte)

00

04

6

Data 2 (Low Byte)

00

84

7 – 8

Data 3 – 4

00

00

1) Possible causes J page 91