Installation

MN05013001E

22

Transfer rates – automatic
baud rate detection

The EZ204-DP module automatically detects the baud rate

used in the communication network after it is switched on.

However, this requires that at least one station sends valid

telegrams in the network.
The EZ204-DP module detects the transfer rate automatically.

The following transfer rates are supported:
• 9.6 Kbit/s to 12000 Kbit/s

Maximum distances/bus
cable lengths

Two types of bus cable are specified in IEC 61158. Cable type

B should no longer be used with new applications because it

is obsolete. Cable type A allows all transfer rates up to

12000 Kbit/s to be used. Cables for burial in the ground,

festoon suspension and drum cables are also available.
The cable parameters are as follows:

The cable parameters specified allow the following bus

segment lengths.

Parameters

Cable type A

Surge impedance in Ω

135 ... 165 at 3 ... 20 MHz

Effective capacitance (pF/m)

< 30

Loop resistance (Ω/km)

< 110

Core diameter (mm)

> 0.64

Core cross-section (mm

2

)

> 0.34