Read/write image data

For more information visit: www.EatonElectrical.com

MN05013001E

103

Read local analog inputs IA1 to IA4
The analog inputs on the EZ800 and EZD basic units can be

read directly via PROFIBUS-DP. The 16-bit value is

transferred in Intel format (LowByte first).
Telegram structure

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 94

1

Command: Read

91

Response:

Read successful

C2

Command

rejected

C0

2

Len

02

02

3

Type

02

02

4

Index

01 – 04

1

01 – 04

1

5

Data 1 (Low Byte)

00

See example

6

Data 2 (High Byte)

00

See example

7 – 8

Data 3 – 4

00

00

1) 01 = Analog input I7

02 = Analog input I8

03 = Analog input I11

04 = Analog input I12