Control commands for EZ700

MN05013001E

76

Counter relays: C1 – C16

Telegram structure

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

J

page 44

1

Command:

Read

89

Write

8D

Response:

Read successful

C2

Write successful

C1

Command rejected

C0

1

2

Type

8F

8F

3

Instance

2

00 – 0F

00 – 0F

4

Index

J

Table 27

5 – 8

Data 1 – 4

depending on index,J Table 28

1) Possible causes J page 91
2) EZ provides 16 counters C1 to C16 for use as required. These can be

addressed using the instance (0 – F).