EZ800/EZD Control Commands

MN05013001E

158

Table 93: Index 0 – Bit IO

The data in the following table is shown in the Motorola format

although it is actually transferred in Intel format.

Table 94: Index 2 – 5, Parameter channels A – D

Example

The channel A parameters of year time switch HY14 are to be

written.

Bit 7 6 5 4 3

2

1

0

FB output Data 3

– – – – –

Q

1

1) Status 1 if the switch-on condition is fulfilled.

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Date 2

Date 1

ON

y6 y5 y4 y3 y2 y1 y0 m3 m2 m1 m0 d4 d3 d2 d1 d0
Year

Month

Day

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Date 4

Date 3

OFF

y6 y5 y4 y3 y2 y1 y0 m3 m2 m1 m0 d4 d3 d2 d1 d0
Year

Month

Day

d4 ... d0: Day (1 .. 31), m3 ... m0: Month (1 .. 12), y6 ... y0: Year (0: 2000 .. 99: 2099)

Index 2 – 5, Parameter channels A – D

Bit

7

6

5

4

3

2

1

0

7

6

5

4

3

2

1

0

Date 2

Date 1

ON

0

0

0

0

0

1

1

0

1

1

0

0

1

1

1

0

Year

Month

Day

Switch-on time:

Day = 14 = 0E

hex

=

000

0 1110b

Month = 6 (June) = 06

hex

=

0000

0110b

Year =

20

03 = 03

hex

=

0

000 0011b