Read/write image data

For more information visit: www.EatonElectrical.com

MN05013001E

119

Example 2

Write marker word MW32 with 823
823

dec

= 337

hex

J

Data 1 = 37

hex

, Data 2 = 03

hex

Byte

Meaning

Value (hex), sent by

Master

Slave

0

Toggle byte

81

80

1

Command: Write

B1

Response:

Write successful

C1

2

Len

02

02

3

Type

0D

0D

4 Index

20

20

5

Data 1

37

00

6

Data 2

03

00

7

Data 3

00

00

8

Data 4

00

00

Advertising