Setting the temperature system, Setting the temperature system using the web agent – Avaya Cajun P882 User Manual

Page 111

Advertising
background image

Cajun P550/P880/P882 Switch User Guide

Configuring System Information

3-13

Setting the Temperature System

You can set the upper and lower temperature warning systems for
your switch’s backplane and slot 1. These warning systems cause the
following to happen if the temperatures you set are reached:

The Supervisor modules shut down the switching modules if
the temperature reaches the Shutdown temperature.

The modules are restarted if the temperature goes below the
Upper Warning Temperature.

The default Shutdown temperatures are conservative for the slot 1
sensor (50° C and backplane sensor (50° C. They can be safely set to
60° C, but settings higher than 60° C are not recommended. You can
set the shutdown temperature to a value lower than 50° C to ensure
prompt notification if a fan fails.

You can set the temperature system using either the web agent or
the CLI.

Setting the
Temperature
System Using
the Web Agent

To configure the temperature warning systems using the Web
Agent:

1. Select Temperature from the System > Configuration group

on the web agent window. The Temperature System dialog
box opens with the current temperature settings (Figure 3-
7).

Figure 3-7. Temperature System Window