P O W E R R E Q U I R E M E N T S

Locations Using 50 Hz Power (Locations Other than North America and Japan)

Version 2

Model 200iP/250iP Motorcycl Pit Dynamometer Installation Guide

B-7

LOCATIONS USING 50 HZ POWER (LOCATIONS OTHER THAN NORTH AMERICA

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

AND JAPAN)

The next section of this appendix contains the power requirements and instructions
for dyno installations excluding North America and 60 Hz areas of Japan.

Note: Refer to page B-2 for power requirements and instructions for North
America and Japan.

To ensure safety and accuracy in the procedures, perform the procedures as they are
described.
The model 200iP/250iP dynamometer (excluding North America and Japan) requires a
dedicated wall receptacle which must be wired for operation and is included with the
dyno or may be shipped in advanced in a separate package. The dyno is equipped
with a power cord with a three-pin IEC plug pre-wired on the end. Refer to Figure 2-
34 on page 32 for the
location and instructions on routing the power cord.
The model 200iP/250iP dynamometer requires a dedicated 240VAC single phase
power outlet rated for 30A for proper operation. Failure to follow these
instructions could result in personal injury or damage to the dyno.
Connecting
the dyno to the incorrect voltage will void the dyno warranty. Contact Dynojet with
any questions.
The dedicated wall receptacle is a three-pin IEC grounded 30A type and must be
wired in accordance with local building codes and requirements. Installation may
require a licensed electrician to conform to applicable safety standards.

If you are installing your dyno in a location other than North America or Japan
and the dyno is not equipped with a three pin IEC grounded plug, contact
Dynojet before attempting to connect the dyno.

Local and national electrical codes will require that the box containing the receptacle
is grounded.

• This circuit should have a dedicated 30A double pole circuit breaker.
• The dyno should be the only device connected to this circuit.
• It may be necessary to install a delayed trip breaker due to the inrush current

drawn by the high pressure blowers.