Installation planning factors, Installation planning factors -13 – Carrier Access Broadmore 1750 User Manual

Page 63

Advertising
background image

Broadmore 1750 - Release 4.6

2-13

Planning

and

Ordering Guide

Installation Planning Factors

Installation Planning Factors

The Broadmore 1750 is designed and delivered ready for installation in a standard 19"
or 23" relay or EIA equipment rack. Several factors should be considered and some
decisions made to ensure a smooth installation that meets all requirements. Installation
factors and system specifications are shown in the following tables.

Factor

Consideration

Access
Clearance

Broadmore 1750 requires the following access clearances for
service and maintenance:

Front: 24"

Rear: 4"

Top: 1.75" (Broadmore 1750 units may be stacked without this
clearance.)

Power
Source

DC Power: –48 VDC at 5 amperes is connected to the rear of the
Broadmore chassis. A second –48 VDC source may be connected
for redundancy.

Optional AC Power Supply Tray: Converts 110/240 VAC (50-60
Hz) to –48 VDC. Rack mounted tray (3.5" high) installs
immediately below Broadmore chassis and can hold two power
supplies. Unit comes with one power supply and cables. A second
power supply with cables can be added to provide redundant DC
power to the Broadmore. AC and DC power connections are at the
rear of the unit. The DC cable is approximately 3.5 ft. long.