Modular Block System: Burner Management

Standard Function Blocks

SB155: Pre-purge

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte-constants KB 001 ... KB 200
(further information about the

SSNR can be found in the

sections “Administration data blocks DB015, DB016 and
DB017” and the “Input Parameter

SSNR” in chapter 5).

Value of DW0000/DB015 = 0: no error present

NEXT:

NEXT = 1: activate “pre-purge” step

COND:

Limit switch for maximum position of the air damper or monitor
maximum air flow
COND = 1: Limit switch is operated

Output parameters

ENBL:

Enable flag bit
ENBL = 1: this function is fault-free
(refer also to Programming guidelines)

RDY:

Ready signal
RDY = 1: “Pre-purge” is active

Function

Monitoring the limit switches for the maximum position of the air damper or
the maximum air flow during the pre-purge time.

SB155

PREPURGE

B - SSNR
X - NEXT
X - COND

ENBL - X

RDY - X